Types-How-to-Select

A plastic pipeline is only as easy to maintain as its joints. A valve that cannot be removed without cutting pipe, a threaded end pushed past its pressure limit, or a seal that does not suit the fluid can turn a ten-minute job into a shutdown. Fittings and unions are small parts, and they are often chosen last. This guide explains the common types, the materials they are made from, and a practical way to select them.

What is a union, and why is it used?

A union is a three-piece fitting. It lets a line be opened without unthreading the pipe connections, so the pipe stays where it is while the section beside it is serviced [3]. Two end pieces remain attached to the pipe, a nut pulls them together, and a seal sits between the faces [9].

The same idea is built into true union ball valves. Both ends of the valve can be released, and the valve body is lifted out while the pipework stays in place. One manufacturer describes a double union and double block design that allows in-line maintenance without disconnecting the pipe [9]. Another states that its valves are blocked in both directions, so the unions can be taken apart from either side [8]. Yukon Industries lists UPVC true union designs in its ball valve range, and a standalone UPVC union pipe connector is also available for pipe-to-pipe connections.

Main types of non-metallic fittings and unions

Most fittings are grouped by the way they connect to the pipe.

●  Socket (solvent-weld) ends. The pipe is pushed into a socket after primer and solvent cement have been applied. For PVC, solvent cementing, threading and flanging are the accepted joining methods [2].
●  Threaded ends. In PVC, threading is done on Schedule 80 pipe only [2]. Threaded fittings are rated at 50% of the pressure rating of a solvent-cemented system [2], and one supplier gives the same limit in terms of the pipe's own rating [3].
●  Flanged ends. Flanged joints are bolted together and can be opened without cutting pipe. In one supplier's PVC data, flanged fittings are rated at 150 psi [2]. Spare flanges are available in UPVC and CPVC.
●  Union ends. Union fittings are offered with socket and threaded ends [3]. In the same PVC data, union fittings are rated at 235 psi [2].
●  Special-purpose fittings. Tank connectors, flexible expansion joints and sampling valves belong here. The full list can be browsed on the fittings page.

Materials: PVC, CPVC, PP and PVDF

The body material decides how hot the fluid may be and which chemicals can be handled. The figures below are supplier-published limits and are meant as a starting point only.

MaterialMaximum service temperatureUsual joining methodsNotes
PVC (UPVC)140°F (60°C) [1]Solvent cement, threading, flanging [2]Resistant to most acids, bases and salts [2]
CPVCUp to 210°F (about 99°C) [1]Solvent welding, threading, flanging [1]Higher cost, so it is mostly used for hot fluids [5]
PP (polypropylene)180°F (82°C) [4]Heat fusion, threading, flanging [4]Suited to drainage carrying mixed acids, bases and solvents [1]
PVDF280°F (138°C) [4]Heat fusion, threading, flanging [4]Not recommended for strong caustics [1]

Published limits are not identical everywhere. One supplier lists copolymer polypropylene as usable up to 200°F [1], while another gives 180°F for natural homopolymer [4]. Grade and manufacturer matter, and the datasheet of the actual product should always be treated as the final word. A longer comparison is available in Yukon's guide to UPVC vs CPVC vs PP valves, and the temperature rating guide covers hot-service limits in more detail.

The seal matters as much as the body

In union-type valves and fittings, the O-ring is usually the only part that touches the fluid and is not plastic. EPDM and FKM (often sold as Viton) are the two seal materials commonly offered [8][9]. A body that resists a chemical can still be let down by a seal that swells, softens or hardens in contact with it, so the chemical resistance chart should be checked for the seal and the body together. The corrosion-resistant plastic valves article explains why material choice is so important in chemical lines.

Pressure rating: the weakest part sets the limit

When valves, flanges or unions are added to a pipe system, the whole system must be de-rated to the lowest-rated component [2]. A pipe that is good for a high pressure does not make the line good for that pressure if one threaded fitting is in it.

Ratings are also specific to the product. One true union ball valve is listed at 150 psi for water at 73°F, with a working temperature range of -4°F to 140°F [9]. A different manufacturer lists 230 psi for its PVC, CPVC and PVDF valves [8]. Both figures can be correct, because they belong to different designs. Plastic fittings should also never be used with compressed air or gas [3].

Thermal expansion

Plastic pipe moves more than most people expect. For PVC, an allowance of 3/8 inch per 10°F change in temperature per 100 feet of pipe is recommended, and for CPVC the figure is 1/2 inch [6]. Worked from that rule, a 100-foot PVC run that swings by 40°F will change in length by about 1.5 inches.

On long straight runs, outdoor lines or hot service, that movement has to go somewhere. If it is not absorbed, it is passed on to fittings and unions. Expansion joints are one way of handling it, and a flexible rubber expansion joint is part of Yukon's fittings range.

Installation habits that prevent leaks

●  Primer is applied before cement. It prepares the surface of the pipe and fitting, and its effect on set and cure time depends on the cement, pipe size, application method, temperature and humidity [7].
●  Cement is applied while the primer is still wet, and excess cement is wiped from the joint [10].
●  In damp or humid weather, 50% more set and cure time is recommended [10]. A joint should not be pressurised before the cure period is over.
●  Threaded joints are made only where the system is rated for them, since their pressure limit is lower [2].
●  Unions are best placed beside valves, pumps and filters, where the line is most likely to be opened again.

Routine inspection also helps. Yukon's valve maintenance and troubleshooting guide lists what is worth checking at regular intervals.

How to select: five questions

1What fluid is being carried?

The chemical, its concentration and its temperature should be checked against resistance charts for both the body and the seal.

2How hot does it get?

PVC is limited to 140°F [1], so CPVC is considered for hotter lines [1][5]. PP and PVDF extend the range further or suit particular chemicals [1][4].

3What is the working pressure?

The lowest-rated component sets the limit for the whole line [2], and threaded ends carry a lower rating than solvent-cemented ones [2].

4Will the line need to be opened?

Where valves, filters or instruments will be serviced, unions or flanges are preferred over permanent socket joints. Where a line is never touched, socket joints are simpler.

5Do the ends match the existing system?

Socket, flange and thread types, as well as thread standards such as NPT or BSP, must match the pipe already installed. Yukon states that its products are ANSI and DIN approved, with JIS available on request.

If the answers are not clear, the Yukon team can be reached through the contact page, and the full product catalogue can be downloaded for sizes and ratings. Working from the fluid, temperature and pressure first usually narrows the choice to one or two materials. The union and end type can then be decided from how the line will be serviced.

Sources

1Hipco. "Basic Materials Guide." https://www.hipco.com/resources/basic-materials-guide/
2Hipco. "Van Stone Flange, Socket, PVC, Schedule 80" (product page with pressure-rating notes). https://store.hipco.com/product/854-180S
3McMaster-Carr. "PVC Pipe Unions." https://www.mcmaster.com/products/pvc-pipe-unions/
4Plastomatic. "Materials." https://plastomatic.com/materials.html
5National Research Council Canada. "Plastic Piping Systems" (Canadian Building Digest 220). https://web.mit.edu/parmstr/Public/NRCan/CanBldgDigests/cbd220_e.html
6Spears Manufacturing. "PVC & CPVC Schedule 80 Expansion Joint / Repair Coupling." https://www.spearsmfg.com/listings_approvals/015_EJ-3A-0816_1021_web.pdf
7ASTM International. "F656-25: Standard Specification for Primers for Use in Solvent Cement Joints of PVC and CPVC Plastic Pipe and Fittings." https://store.astm.org/f0656-25.html
8Nassau National Cable. "Type 21 True Union PVC Ball Valve 1604015." https://nassaunationalcable.com/products/1-1-2-type-21-flange-ends-true-epdm-o-rings-pvc-union-ball-valve-1604015
9American Granby. "SCH 80 PVC True Union Ball Valve ITUV100SE" (via Pool360). https://www.pool360.com/Product/pool-amg-56-4356
10IPS Corporation. "Weld-On Solvent Cement Welding Guide." https://weldon.com/wp-content/uploads/2015/03/solvent_welding_guide_cartoon_2013.pdf
Sidebar
Start typing to see posts you are looking for.